Mounting and Wiring

Product image


SRI8200-8A8DOH COE Parameter Query

Object dictionary Sub-index Name Data Type Description

0x2001

0x01

EtherCATBUSErrOutputEN

Byte

This parameter is used to set the action of the digital and analog output channels after the coupler's EtherCAT communication is disconnected:

0: Output hold, cleared after 50 ms

1: Output hold

2: Output hold, cleared after 10 ms

3: Output hold, cleared after 20 ms

4: Output hold, cleared after 100 ms

5: Output hold, cleared after 500 ms

6: Output cleared immediately

0x2002 0x01 ExtNum Byte Number of connected IO-Link slave modules

0x02

LocalErr

Byte

Local master module system fault information:

0: No fault

1: System fault

0x03 to 0x0A

EM1Err–EM8Err

Byte

IO-Link slave module connection information:

0: Connected slave mode;

1: Slave module not connected or not configured.

0x2005 to 0x200C

 

 

 

 

 

0x01 index Word ISDU index of the IO-Link slave connected to ports X01–X08.
0x02 subindex Byte ISDU sub-index of the IO-Link slave connected to ports X01–X08.
0x03 Parameter length Byte Data width of the IO-Link slave connected to ports X01–X08 (max. 32 bytes)
0x04 Write Byte Write (value 1 is valid); after it is set to 1 successfully, the value is automatically reset to 0.
0x05 Read Byte Read (value 1 is valid); after it is set to 1 successfully, the value is automatically reset to 0.
0x06~0x25 byte1~byte32 Byte Parameter configuration of the IO-Link slaves connected to ports X01~X08.

0x200D to 0x2014

 

 

 

 

 

 

0x01 event length Word Total number of master-side events already present on ports X01–X08; a maximum of 255 are stored at the same time, and when full, the oldest ones are overwritten.
0x02 event index Word Event index to be queried for ports X01–X08; if the entered value exceeds the maximum count, the last one is read.
0x03 Life cycle Word Power-up count of ports X01–X08; a maximum of 255 counts are stored at the same time, and counting restarts from zero when full.
0x04 run time Dword Power-on run time of ports X01~X08, in seconds; cleared on power-down.

0x05

Event mode type

Word

Bit7~Bit4 is mode:

0001: single short;

0010: disappeared;

0011: appeared;

Bit3~Bit0 is type:

0001: Notification;

0010: Warning;

0011: Error;

0X06 Event code word Master event codes of ports X01–X08; see the table "IO-Link Master EVENT CODE" for details.
0x07 Clear Word Clear all master-side events of ports X01–X08 (value 1 is valid); after it is set to 1 successfully, the value is automatically reset to 0.

0x2015 to 0x201C

0x01 event length Word Total number of slave-side events already present on ports X01–X08; a maximum of 255 are stored at the same time, and when full, the oldest ones are overwritten.
0x02 event index Word Event index to be queried for ports X01–X08; if the entered value exceeds the maximum count, the last one is read.
0x03 Life cycle Word Power-up count of ports X01–X08; a maximum of 255 counts are stored at the same time, and counting restarts from zero when full.
0x04 run time Dword Power-on run time of ports X01~X08, in seconds; cleared on power-down.

0x05

Event mode type

Word

Bit7~Bit4 is mode:

0001: single short;

0010: disappeared;

0011: appeared;

Bit3~Bit0 is type:

0001: Notification;

0010: Warning;

0011: Error;

0X06 Event code word Slave event codes of ports X01–X08; the event codes are defined by the connected IO-Link slave modules.
0x07 Clear Word Clear all slave-side events of ports X01–X08 (value 1 is valid); after it is set to 1 successfully, the value is automatically reset to 0.

0x4000 to 0x4070

 

 

 

 

 

 

0x01

Control

Byte

Control command:

0: no control

2: write

3: read

0x02

Status

Byte

Status feedback:

0: no activity

1: busy

2: success

4: error

0xFF: failure

0x03 Index Word ISDU index of the IO-Link slave connected to ports X01–X08.
0x04 Subindex Byte ISDU sub-index of the IO-Link slave connected to ports X01–X08.
0x05 Length Byte Data length (max 232 bytes supported)
0X06 Data ARRAY[0..231]OF BYTE Data
0x07 Error Code Word Error code 3.4.4 Error code query
0x6000 0x01 ID Word Coupler EtherCAT station address