Menu

Indicator Description

Indicator Description

 

Indicator Description

Module status indicator
Indicator Status Description
US (system power indicator) Green steady on Us powered normally
Yellow indicator steady on Under normal power supply, Us undervoltage (undervoltage is indicated when below 17 V)
Off Us not powered
Note: When Ua is powered normally and Us is not powered, the Us indicator does not light red as an indication but remains off
UA (peripheral power supply indicator) Green steady on Ua powered normally
Yellow indicator steady on Under normal power supply, Ua undervoltage (undervoltage is indicated when below 17 V)
Off Ua not powered
Note: When Us is powered normally and Ua is not powered, the Ua indicator lights red as a reminder
BF (communication indicator) Red indicator steady on EtherNet/IP communication failure
Red indicator off EtherNet/IP communication normal
SF Red indicator steady on Configured byte count inconsistent with the actually connected module byte count (configuration error)
Red blinking (1 Hz) IO-Link configuration error: the configured bytes are fewer than the IO-Link slave's input/output bytes, or the configured model is inconsistent with the actually connected model; IO-Link configuration exceeds 32 bytes
Red blinking (5 Hz) IO-Link digital slave DO output short circuit
Red indicator off No error
XF1 XF1 port communication indicator: the indicator lighting up indicates an XF1 port communication connection
XF2 XF2 port communication indicator: the indicator lighting up indicates an XF2 port communication connection
Port indicator
Indicator Status Description

00 indicator (IO-Link mode PIN4)
Green indicator steady on IO-Link communication connection normal
Green blinking (1 Hz) IO-Link communication connection abnormal
Green indicator off IO-Link mode not enabled
Red blinking (1 Hz) 1. IO-Link configuration error on this port
2. Port IO-Link slave undervoltage
Red blinking (5 Hz) IO short circuit on the IO-Link digital slave
Red indicator steady on IO-Link PIN4 communication line short circuit
01 indicator (IO-Link mode PIN2) In Class A mode
Green indicator steady on PIN2 has PNP signal input or output
Green indicator off PIN2 has no PNP signal input or output
Red indicator steady on PIN2 short circuit
In Class B mode
Green indicator steady on PIN2 has 24 V output
Green indicator off PIN2 has no 24 V output
Red indicator steady on PIN2 short circuit
00 and 01 indicators (PNP input mode) 00 indicator (PIN4)
Green indicator steady on PIN4 has PNP signal input
Green indicator off PIN4 has no PNP signal input
01 indicator (PIN2)
Green indicator steady on PIN2 has PNP signal input or output
Green indicator off PIN2 has no PNP signal input or output
Red indicator steady on PIN2 short circuit
00 indicator (PNP/NPN output mode) 00 indicator (PIN4)
Green indicator off PIN4 has no signal output
Green indicator steady on PIN4 has signal output
Red indicator steady on PIN4 short circuit
01 indicator (PIN2)
Green indicator steady on PIN2 has PNP signal input or output
Green indicator off PIN2 has no PNP signal input or output
Red indicator steady on PIN2 short circuit
00 and 01 indicators (fault status) IO-Link mode
00 and 01 red indicators blinking simultaneously (1 Hz) Power PIN1 short circuit
PNP/NPN output mode, PNP input mode
00 and 01 red indicators blinking simultaneously (1 Hz) Power PIN1 short circuit

 