Indicator Description
| Indicator | Description |
| US |
Coupler power indicator: ① Green steady on: US powered normally; ② Off: US not powered; ③ Yellow indicator steady on: US undervoltage under normal power supply (indicated when below 20 V) Note: When UA is powered normally and US is not powered, the US indicator does not light red as an indication but remains off |
| UA |
Peripheral power supply indicator: ① Green steady on: UA powered normally; ② Off: UA not powered; ③ Yellow indicator steady on: UA undervoltage while US is powered normally (undervoltage is indicated when the voltage drops below 20 V) Note: When US is powered normally and UA is not powered, the UA indicator lights red as a reminder |
| BF |
Communication indicator: Red indicator steady on: EtherCAT communication failure Red indicator off: EtherCAT communication normal |
| SF |
① Red indicator flashing (1 Hz): IO-Link configuration error—the configured bytes are fewer than the slave attributes (input/output byte counts), or the configured model is inconsistent with the actually connected model; IO-Link configuration exceeds 32 bytes ② Red blinking (5 Hz): IO-Link slave digital DO output short circuit ③ Red indicator off: No error. |
| XF1 |
XF1 communication indicator: the green indicator lights up to indicate the XF1 communication connection. |
| XF2 |
XF2 communication indicator: the green indicator lights up to indicate the XF2 communication connection. |
| 00 indicator of X01~X08 (IO-Link mode) |
IO-Link communication indicator: ① Green indicator steady on: IO-Link communication connection normal; ② Green blinking (1 Hz): IO-Link communication connection abnormal; ③ Green indicator off: IO-Link mode not enabled ④ Red blinking (1 Hz): 1. IO-Link configuration error on this port; 2. Port IO-Link slave undervoltage ⑤ Red LED flashing (5 Hz): IO short circuit on the IO-Link digital slave or on the DO extension module behind the slave ⑥ Red indicator steady on: IO-Link PIN4 communication line short circuit |
| 01 indicator of X01~X08 (IO-Link mode) |
PIN2 signal indicator In Class A mode: ① Green indicator steady on: PIN2 has PNP signal input or output ② Green indicator off: PIN2 has no PNP signal input or output ③ Red indicator steady on: PIN2 short circuit In Class B mode: ① Green indicator steady on: PIN2 has 24 V output ② Green indicator off: PIN2 has no 24 V output ③ Red indicator steady on: PIN2 short circuit |
| 00 and 01 indicators of X01~X08 (PNP input mode) |
00 indicator: ① Green indicator steady on: PIN4 has PNP signal input ② Green indicator off: PIN4 has no PNP signal input 01 indicator: ① Green indicator steady on: PIN2 has PNP signal input or output ② Green indicator off: PIN2 has no PNP signal input or output ③ Red indicator steady on: PIN2 short circuit |
| 00 indicator of X01~X08 (PNP/NPN output mode) |
00 indicator: ① Green indicator off: PIN4 has no signal output ② Green indicator steady on: PIN4 has signal output ③ Red indicator steady on: PIN4 short circuit 01 indicator: ① Green indicator steady on: PIN2 has PNP signal input or output ② Green indicator off: PIN2 has no PNP signal input or output ③ Red indicator steady on: PIN2 short circuit |
| 00 and 01 indicators of X01~X08 (fault status) |
IO-Link mode: 00 and 01 red indicators blinking simultaneously (1 Hz): power PIN1 short circuit PNP/NPN output mode, PNP input mode: 00 and 01 red indicators blinking simultaneously (1 Hz): power PIN1 short circuit |