Indicator Description
| Indicator | Description |
| US (green) |
Coupler power indicator: ① Green steady on: US powered normally; ② Off: US not powered; ③ Yellow indicator steady on: US undervoltage under normal power supply (indicated when below 20 V) Note: When UA is powered normally and US is not powered, the US indicator does not light red as an indication but remains off |
| UA (green) |
Peripheral power supply indicator: ① Green steady on: UA powered normally; ② Off: UA not powered; ③ Yellow indicator steady on: UA undervoltage while US is powered normally (undervoltage is indicated when the voltage drops below 20 V) Note: When US is powered normally and UA is not powered, the UA indicator lights red as a reminder |
| BF (red) |
Network communication indicator: Steady on: network communication failure; Off: network communication normal; |
| SF (red) |
Flashing (1 Hz): IO-Link configuration error; the configured bytes are fewer than the slave properties (input/output byte count) (at the same time, the 00 red indicator of the corresponding port flashes at 1 Hz) Flashing (5 Hz): IO-Link slave digital DO output short circuit Off: no error. |
| XF1 (green) |
XF1 port communication indicator: the green indicator flashing indicates that the XF1 port is connected for communication. |
| XF2 (green) |
XF2 port communication indicator: the green indicator flashing indicates that the XF2 port is connected for communication. |
| 00 indicator of X01~X08 (IO-Link mode) |
IO-Link communication indicator: ① Green indicator steady on: IO-Link communication connection normal; ② Green indicator flashing (1 Hz): IO-Link communication connection abnormal; ③ Green indicator off: IO-Link not enabled ④ Red LED flashing (5 Hz): IO short circuit on the IO-Link digital slave ⑤ Red indicator steady on: IO-Link PIN4 communication line short circuit |
| 01 indicator of X01~X08 (IO-Link mode) |
PIN2 signal indicator In Class A mode: ① Green indicator steady on: PIN2 has PNP signal input or output ② Green indicator off: PIN2 has no PNP signal input or output ③ Red indicator steady on: PIN2 short circuit In Class B mode: ① Green indicator steady on: PIN2 has 24 V output ② Green indicator off: PIN2 has no 24 V output ③ Red indicator steady on: PIN2 short circuit |
| 00 and 01 indicators of X01~X08 (PNP input mode) |
00 indicator: ① Green indicator steady on: PNP signal input present on PIN4 ② Green indicator off: PIN4 has no PNP signal input
01 indicator: ① Green indicator steady on: PIN2 has PNP signal input or output ② Green indicator off: PIN2 has no PNP signal input or output ③ Red indicator steady on: PIN2 short circuit
|
| 00 indicator of X01~X08 (PNP/NPN output mode) |
00 indicator: ① Green indicator off: PIN4 has no signal output ② Green indicator steady on: signal output present on PIN 4 ③ Red indicator steady on: PIN 4 short circuit
01 indicator: ① Green indicator steady on: PIN2 has PNP signal input or output ② Green indicator off: PIN2 has no PNP signal input or output ③ Red indicator steady on: PIN2 short circuit |
| 00 and 01 indicators of X01~X08 (fault status) |
IO-Link mode: 00 and 01 red indicators flashing simultaneously (1 Hz): power PIN 1 short circuit 00 Red indicator flashing (1 Hz): IO-Link configuration error PNP/NPN output mode, PNP input mode: 00 and 01 red indicators flashing simultaneously (1 Hz): power PIN 1 short circuit |