Indicator Description
| Indicator | Description |
| US |
Coupler power indicator: ① Green steady on: US powered normally; ② Off: US not powered; ③ Yellow indicator steady on: US undervoltage under normal power supply (indicated when below 20 V) Note: When UA is powered normally and US is not powered, the US indicator does not light red as an indication but remains off |
| UA |
Peripheral power supply indicator: ① Green steady on: UA powered normally; ② Off: UA not powered; ③ Yellow indicator steady on: UA undervoltage while US is powered normally (undervoltage is indicated when the voltage drops below 20 V) Note: When US is powered normally and UA is not powered, the UA indicator lights red as a reminder |
| BF |
EtherNet/IP communication indicator: ① Red indicator steady on: EtherNet/IP communication fault; ② Red indicator off: EtherNet/IP communication normal; |
| SF |
① Red indicator steady on: the byte count of the configured modules is inconsistent with the actual connection (configuration error) ② Red indicator flashing (1 Hz): IO-Link configuration error, when the configured bytes are fewer than the IO-Link slave's input/output bytes or the configured model is inconsistent with the actually connected model; IO-Link configuration exceeds 32 bytes; ③ Red indicator flashing (5 Hz): IO-Link digital slave DO output short circuit; ④ Red indicator off: no error. |
| XF1 |
XF1 port communication indicator: the indicator lights up to indicate that the XF1 port is connected for communication. |
| XF2 |
XF2 port communication indicator: the indicator lights up to indicate that the XF2 port is connected for communication. |
| 00 indicator of X01~X08 (IO-Link mode) |
IO-Link communication indicator: ① Green indicator steady on: IO-Link communication connection normal; ② Green blinking (1 Hz): IO-Link communication connection abnormal; ③ Green indicator off: IO-Link not enabled; ④ Red blinking (1 Hz): 1. IO-Link configuration error on this port; 2. Port IO-Link slave undervoltage; ⑤ Red LED flashing (5 Hz): IO short circuit on the IO-Link digital slave; ⑥ Red indicator steady on: IO-Link PIN4 communication line short circuit; |
| 01 indicator of X01~X08 (IO-Link mode) |
PIN2 signal indicator In Class A mode: ① Green indicator steady on: PIN2 has PNP signal input or output ② Green indicator off: PIN2 has no PNP signal input or output ③ Red indicator steady on: PIN2 short circuit In Class B mode: ① Green indicator steady on: PIN2 has 24 V output ② Green indicator off: PIN2 has no 24 V output ③ Red indicator steady on: PIN2 short circuit |
| 00 and 01 indicators of X01~X08 (PNP input mode) |
00 indicator: ① Green indicator steady on: PNP input present on PIN4; ② Green indicator off: no PNP input on PIN4; 01 indicator: ① Green indicator steady on: PIN2 has PNP signal input or output ② Green indicator off: PIN2 has no PNP signal input or output ③ Red indicator steady on: PIN2 short circuit |
| 00 indicator of X01~X08 (PNP/NPN output mode) |
00 indicator: ① Green indicator off: no output on PIN 4; ② Green indicator steady on: output present on PIN 4; ③ Red indicator steady on: PIN 4 short circuit; 01 indicator: ① Green indicator steady on: PIN2 has PNP signal input or output ② Green indicator off: PIN2 has no PNP signal input or output ③ Red indicator steady on: PIN2 short circuit |
| 00 and 01 indicators of X01~X08 (fault status) |
IO-Link mode: 00 and 01 red indicators flashing simultaneously (1 Hz): power PIN 1 short circuit; 00 Red indicator flashing (1 Hz): IO-Link configuration error; PNP/NPN output mode, PNP input mode: 00 and 01 red indicators flashing simultaneously (1 Hz): power PIN 1 short circuit; |