Technical Specifications
| Product Model |
SC4224 |
| Technical specifications |
| Number of output channels |
4 |
| Power electronic device supply voltage |
24 V DC (via a signal distribution board) |
| Measurement type |
Voltage type |
| Voltage range |
0V...10V |
| Distributed clock |
Yes |
| Distributed clock accuracy |
<< 1 μs |
| Load |
> 5 kΩ (short-circuit protection) |
| Measurement error |
< 0.1% (relative to the full scale value) |
| Output error |
<±0.1% (relative to the final value) |
| Resolution |
| Resolution |
16-bit |
| Electrical isolation |
500 V (S-bus/signal voltage) |
| Conversion time |
~ 400 μs |
| Auxiliary power supply current |
Typical value 25 mA |
| S-bus current consumption |
Typical value 90 mA |
| Features |
Optional watchdog; user-defined value output with ramp function; user calibration supported |
| Operating environment |
Operating environment temperature: -20~60°C, relative humidity: 5%~90% (Non-condensing) |
| Storage temperature |
-40~60 °C |
| Dimensions (L × W × H) |
12×66×55(mm) |