Technical Specifications
Interface Parameters |
Bus protocol |
Transfer Rate |
Station Type |
Rated voltage of bus input power |
Rated Current Consumption |
Power Consumption |
Power Supply |
Common Parameters |
Specification and dimension |
Weight |
Operating temperature |
Storage temperature |
Relative humidity |
Degree of protection |
Number of channels |
4 |
Sensor Type |
Thermocouple |
Connection mode |
2-wire system |
Corresponding range of the sensor |
B: 50~1800°C C: (reserved) E: -200~1000°C J: -200~1200°C K: -200~1370°C L: (reserved) N: (reserved) R: (reserved) S: -50~1690°C T: (reserved) U: (reserved) |
Accuracy |
±0.3% @25°C (F. S.) ±0.5% @-20~60°C (F. S.) |
Sensitivity |
0.1°C |
Resolution |
16 bit (int type) |
Conversion Time |
29ms/ch 115ms/4ch |
Filter |
Single-channel filter, configurable (levels 0~10) |
Wire break detection |
Support |
Wire break detection time |
2 ms |
Misconnection of overvoltage protection |
±30V |
Noise suppression |
50Hz, 60Hz, 10Hz, and no noise suppression |
Excitation current |
<2mA |
Input impedance |
≥10KΩ |
Isolation mode |
Digital isolation |
Isolation withstand voltage |
500VDC |
Channel indicator |
Green LED |
Last modified: 2025-06-30