Interface Parameters
Bus protocol
Transfer Rate
Station Type
Rated voltage of bus input power
Rated Current Consumption
Power Consumption
Power Supply
Common Parameters
Specification and dimension
Weight
Operating temperature
Storage temperature
Relative humidity
Degree of protection

Temperature Input Parameters

Number of channels 4
Sensor Type Thermocouple
Connection mode 2-wire system
Corresponding range of the sensor B: 50~1800°C C: (reserved) E: -200~1000°C J: -200~1200°C K: -200~1370°C L: (reserved) N: (reserved) R: (reserved) S: -50~1690°C T: (reserved) U: (reserved)
Accuracy ±0.3% @25°C (F. S.) ±0.5% @-20~60°C (F. S.)
Sensitivity 0.1°C
Resolution 16 bit (int type)
Conversion Time 29ms/ch 115ms/4ch
Filter Single-channel filter, configurable (levels 0~10)
Wire break detection Support
Wire break detection time 2 ms
Misconnection of overvoltage protection ±30V
Noise suppression 50Hz, 60Hz, 10Hz, and no noise suppression
Excitation current <2mA
Input impedance ≥10KΩ
Isolation mode Digital isolation
Isolation withstand voltage 500VDC
Channel indicator Green LED