Menu

Mounting and Wiring

Wiring Diagram

Note: A+ and A- are voltage signal input channels, and AI+ and AI- are current signal input channels. If CH0 needs to be connected to a voltage signal, it can be connected to A+ and A- terminals; if CH0 needs to be connected to a current signal, it can be connected to AI+ and AI- terminals; both channels are CH0 and occupy the same data address, so only one can be selected for use and both cannot be connected simultaneously. The same rule applies to other input channels. The wiring in the diagram is only an example, and specific connections can be made as needed.

 


Terminal Description

Terminal Description
A+,A- CH0 voltage input terminal
AI+,AI- CH0 current input terminal
B+,B- CH1 voltage input terminal
BI+,BI- CH1 current input terminal
C+,C- CH2 voltage input terminal
CI+,CI- CH2 current input terminal
........ ............
........... ............
H+,H- CH7 voltage input terminal
HI+,HI- CH7 current input terminal

 


COE General Parameter Description

Configuration parameters will not be synchronized to Startup, and will not be saved after power-off or hot-plugging.

Parameters Data type Description
2004:01 Err 24v_nf

Bit0:

1: Channel 24V power supply abnormal

0: Normal

2005:01 Channel Num

0: Enable 4 channels

1: Enable the first channel

2: Enable the first 2 channels

2005:02 Channel Time

Channel update time:

0:400us

1:lms

2:2ms

3:5ms

4:10ms

5:20ms

2005:03 Channel Type

Each Bit corresponds to one channel: e.g.

Bit0: Corresponds to CH0

Bit1: Corresponds to CH1

........

Set a detection value:

0: Voltage ±10V     1: Current 0-20mA

Previous
Indicator Description
Next
SRE3274 | 4 Channel RTD Measurement Module
Last modified: 2025-11-06