Mounting and wiring

Wiring diagrams

 


Terminal description

Terminal block Instructions
R1+ COM1 serial port RS422 signal receive+ COM1 serial port RS485 signal B
T1+ COM1 serial port RS422 signal transmit+ --
R1- COM1 serial port RS422 signal receive- COM1 serial port RS485 signal A
T1- COM1 serial port RS422 signal transmit - --
R2+ COM2 serial port RS422 signal receive + COM2 serial port RS485 signal B
T2+ COM2 serial port RS422 signal transmit + --
R2- COM2 serial port RS422 signal receive - COM2 serial port RS485 signal A
T2- COM2 serial port RS422 signal transmit - --
R3+ COM3 serial port RS422 signal receive + COM3 serial port RS485 signal B
T3+ COM3 serial port RS422 signal transmit + --
R3- COM3 Serial Port RS422 signal receive - COM3 Serial Port RS485 signal A
T3- COM3 Serial Port RS422 signal transmit - --
R4+ COM4 Serial Port RS422 signal receive + COM4 Serial Port RS485 signal B
T4+ COM4 serial port RS422 signal transmit + --
R4- COM4 serial port RS422 signal receive - COM4 serial port RS485 signal A
T4- COM4 serial port RS422 signal transmit - --
R1 COM1 serial port RS-232 receive data input
T1 COM1 serial port RS-232 transmit data output
R2 COM2 serial port RS-232 receive data input
T2 COM2 serial port RS-232 transmit data output
R3 COM3 serial port RS-232 receive data input
T3 COM3 serial port RS-232 transmit data output
R4 COM4 serial port RS-232 receive data input
T4 COM4 serial port RS-232 transmit data output

 


Parameter Description

By default, there are 4 groups of serial port configuration parameters, corresponding to 4 serial ports. All parameter changes take effect immediately without powering off or restarting, as shown below:

Parameters Instructions
Duplex Mode 0: Full Duplex (RS232/RS422)
1: Half Duplex (RS485)
Baudrate Baud Rate:
0:1200
1:2400
2:4800
3:9600
4:19200
5:38400
6:57600
7:115200
Data Bit Data bit:
0:8 bits
1:7 bits
Stop Bit Stop bit:
0:1 bit
1:2 bits
Parity Bit Parity bit:
0: No parity
1: Odd parity
2: Even parity
ReceiveTimeout Serial port receive timeout: 5-200 (unit: ms)
If the value is out of range, it shall be calculated as the maximum value, e.g., a value exceeding 200 is calculated as 200.
Modbus Master ResponseTimeout Modbus RTU master mode response timeout
If the slave station fails to respond within the set time, it is judged as a communication timeout.
5-5000 (unit: ms)
If the value is out of range, it shall be calculated as the maximum value, e.g., a value exceeding 5000 is calculated as 5000.
Modbus Master Scan Time Modbus RTU master mode polling time
The interval between the completion of one command and the next in MBS master mode Unit: ms