Mounting and Wiring

Wiring Diagram


Analog Voltage Pparameters

Voltage Input Range Selection Table

Voltage input range selection and code value range
Range selection Range Code value range Voltage input formula Voltage output formula
0 Disable, indicating the channel is not enabled
1 (default) -10V~+10V -32768~32767 D=(65535/20)*U U=(D*20)/65535
2 0V~10V 0~32767 D=(32767/10)*U U=(D*10)/32767
3 -10V~+10V -27648~27648 D=(55296/20)*U U=(D*20)/55296
4 0V~10V 0~27648 D=(27648/10)*U U=(D*10)/27648
5 -5V~+5V -27648~27648 D=(55296/10)*U U=(D*10)/55296
6 0V~5V 0~27648 D=(27648/5)*U U=(D*5)/27648
7 1V~5V 0~27648 D=(27648/4)*U-6912 U=(D+6912)*4/27648

Note: D represents the code value, and U represents the voltage. The default range for analog voltage input terminal is 1: -10V~+10V (-32768~32767).

 

Voltage Output Range Selection Table

Voltage output range selection and code value range
Range selection Range Code value range Voltage input formula Voltage output formula
0 Disable, indicating the channel is not enabled
1 (default) -10V~+10V -32768~32767 D=(65535/20)*U U=(D*20)/65535
2 0V~10V 0~32767 D=(32767/10)*U U=(D*10)/32767
3 -10V~+10V -27648~27648 D=(55296/20)*U U=(D*20)/55296
4 0V~10V 0~27648 D=(27648/10)*U U=(D*10)/27648
5 -5V~+5V -27648~27648 D=(55296/10)*U U=(D*10)/55296
6 0V~5V 0~27648 D=(27648/5)*U U=(D*5)/27648
7 1V~5V 0~27648 D=(27648/4)*U-6912 U=(D+6912)*4/27648

Note: D represents the code value, and U represents the voltage. The default range for analog voltage output terminal is 1: -10V~+10V (-32768~32767).

 

Voltage Input Code Value Table

Voltage -10V~+10V 0V~10V -10V~+10V 0V~10V
-32768~32767 0~32767 -27648~27648 0~27648
Code value Code value Code value Code value
-10.13 - - -27980 -
-10 -32768 - -27648 -
-9 -29491 - -24883 -
-8 -26214 - -22118 -
-7 -22937 - -19354 -
-6 -19661 - -16589 -
-5 -16384 - -13824 -
-4 -13107 - -11059 -
-3 -9830 - -8294 -
-2 -6554 - -5530 -
-1 -3277 - -2765 -
-0.13 -426 -384 -359 -332
-0.06 -197 -197 -166 -156
0 0 0 0 0
1 3277 3277 2765 2765
2 6554 6554 5530 5530
3 9830 9830 8294 8294
4 13107 13107 11059 11059
5 16384 16384 13824 13824
6 19661 19661 16589 16589
7 22937 22937 19354 19354
8 26214 26214 22118 22118
9 29491 29491 24883 24883
10 32767 32767 27648 27648
10.12 - - 27980 27980
Code value formula Code value = ( 65535/20 ) *Voltage Code value = ( 32767/10 ) *Voltage Code value = ( 55296/20 ) *Voltage Code value = ( 27648/10 ) *Voltage
Voltage formula Voltage = ( Code value*20 )/65535 Voltage = ( Code value*10 )/32767 Voltage = ( Code value*20 )/55296 Voltage = ( Code value*10 )/27648

Note:

① When the voltage input terminal range is selected as -10V~+10V (-32768~32767), it supports overflow/ underflow functions. That is, when the channel input voltage is greater than 10V, it displays the maximum code value 32767; When the input voltage of the input channel is less than -10V, it displays the minimum code value -32768.

② When the voltage input terminal range is selected as 0V~10V (0~32767), it supports underflow overshoot, overflow/underflow, and underflow alarm functions. Overshoot means that when the channel input range exceeds the range and enters overshoot, it displays a normal calculated code value within -0.13V~+10V. Overflow/underflow means that when the channel input voltage exceeds 10V, it displays the maximum code value 32767. When the input voltage of the input channel is less than -0.13V, the module displays the minimum overshoot code value -384 and gives an alarm at the same time .

③ When the voltage input terminal range is selected as -10V~+10V ( -27648~27648), it supports overshoot, overflow/underflow, and overflow/underflow alarm functions. Overshoot means that when the channel input voltage exceeds the range and enters overshoot, the module displays a normal calculated code value within -10.13V~+10.12V. Overflow/underflow means that when the channel input voltage exceeds 10.12V, the module displays the maximum overshoot code value 27980 and gives an alarm at the same time. When the input voltage of the input channel is less than -10.13V, the module displays the minimum overshoot code value  - 27980 and gives an alarm at the same time.

④ When the voltage input terminal range is selected as 0V~10V ( 0~27648), it supports overshoot, overflow/underflow, and overflow/underflow alarm functions. Overshoot means that when the channel input voltage exceeds the range and enters overshoot, the module displays a normal calculated code value within -0.13V~+10.12V. Overflow/underflow means that when the channel input voltage exceeds 10.12V, the module displays the maximum overshoot code value 27980 and gives an alarm at the same time. When the input voltage of the input channel is less than -0.13V, the module displays the minimum overshoot code value  - 332 and gives an alarm at the same time.

 

 
Voltage -5V~+5V 0V~5V 1V~5V
-27648~27648 0~27648 0~27648
Code value Code value Code value
-5.07 -27980 - -
-5 -27648 - -
-4 -22118 - -
-3 -16588 - -
-2 -11060 - -
-1 -5530 - -
-0.07 -332 -332 -
0 0 0 -
0.94 5198 5198 -345
1 5530 5530 0
2 11060 11060 6912
3 16588 16588 13824
4 22118 22118 20736
5 27648 27648 27648
5.06 27980 27980 27933
Code value formula Code value =(55296/10)* Voltage Code value =(27648/5)*Voltage Code value =(27648/4)* Voltage -6912
Voltage formula Voltage =( Code value *10)/55296 Voltage =( Code value *5)/27648 Voltage =( Code value +6912)*4/27648

Note:

① When the voltage input terminal range is selected as -5V~+5V (-27648~27648), it supports overshoot, overflow/underflow, and overflow/underflow alarm functions. Overshoot means that when the channel input voltage exceeds the range and enters overshoot, the module displays a normal calculated code value within -5.07V~+5.06V. Overflow/underflow means that when the channel input voltage exceeds 5.06V, the module displays the maximum overshoot code value 27980 and gives an alarm at the same time; When the input voltage of the input channel is less than -5.07V, the module displays the minimum overshoot code value -27980 and gives an alarm at the same time.

②The voltage input terminal range is selected as 0V~5V ( 0~27648), it supports overshoot, overflow/underflow, and overflow/underflow alarm functions. Overshoot means that when the channel input voltage exceeds the range, the module displays a normal calculated code value within -0.07V~+5.06V. Overflow/underflow means that when the channel input voltage exceeds 5.06V, the module displays the maximum overshoot code value 27980 and gives an alarm at the same time; When the input voltage of the input channel is less than -0.07V, the module displays the minimum overshoot code value  - 332 and gives an alarm at the same time.

③The voltage input terminal range is selected as 1V~5V ( 0~27648), it supports overshoot, overflow/underflow, and overflow/underflow alarm functions. Overshoot means that when the channel input voltage exceeds the range, the module displays a normal calculated code value within 0.94V~5.06V. Overflow/underflow means that when the channel input voltage exceeds 5.06V, the module displays the maximum overshoot code value 27933 and gives an alarm at the same time. When the input voltage of the input channel is less than 0.94V, the module displays the minimum overshoot code value  - 345 and gives an alarm at the same time.

 

Voltage Output Code Value Table

Voltage -10V~+10V 0V~10V -10V~+10V 0V~10V
-32768~32767 0~32767 -27648~27648 0~27648
Code value Code value Code value Code value
-10 -32768 - -27648 -
-9 -29491 - -24883 -
-8 -26214 - -22118 -
-7 -22937 - -19354 -
-6 -19661 - -16589 -
-5 -16384 - -13824 -
-4 -13107 - -11059 -
-3 -9830 - -8294 -
-2 -6554 - -5530 -
-1 -3277 - -2765 -
0 0 0 0 0
1 3277 3277 2765 2765
2 6554 6554 5530 5530
3 9830 9830 8294 8294
4 13107 13107 11059 11059
5 16384 16384 13824 13824
6 19661 19661 16589 16589
7 22937 22937 19354 19354
8 26214 26214 22118 22118
9 29491 29491 24883 24883
10 32767 32767 27648 27648
Code value formula Code value = ( 65535/20 ) *Voltage Code value = ( 32767/10 ) *Voltage Code value = ( 55296/20 ) *Voltage Code value = ( 27648/10 ) *Voltage
Voltage formula Voltage = ( Code value*20 )/65535 Voltage = ( Code value*10 )/32767 Voltage = ( Code value*20 )/55296 Voltage = ( Code value*10 )/27648

Note:

① The voltage output terminal supports overflow/underflow functions. That’s,  when the voltage output terminal range is selected as -10V~+10V or 0V~10V and the code value is set to be greater than the maximum code value corresponding to the range, all channels output 10V;

When the voltage output terminal range is selected as -10V~+10V and the code value is set below the minimum code value corresponding to the range, the channel outputs -10V.

When the voltage output terminal range is selected as 0V~10V and the code value is set below the minimum code value corresponding to the range, the channel outputs 0V.

 

Voltage -5V~+5V 0V~5V 1V~5V
-27648~27648 0~27648 0~27648
Code value Code value Code value
-5 -27648 - -
-4 -22118 - -
-3 -16588 - -
-2 -11060 - -
-1 -5530 - -
0 0 0 -
1 5530 5530 0
2 11060 11060 6912
3 16588 16588 13824
4 22118 22118 20736
5 27648 27648 27648
Code value formula Code value =(55296/10)* Voltage Code value =(27648/5)*Voltage Code value =(27648/4)* Voltage -6912
Voltage formula Voltage =( Code value *10)/55296 Voltage =( Code value *5)/27648 Voltage =( Code value +6912)*4/27648

Note: 

① The voltage output terminal supports overflow/underflow functions. That’s,  when the voltage output terminal range is selected as -5V~+5V/0V~5V/1V~5V and the code value is set to be greater than the maximum code value corresponding to the range, all channels output 5V;

When the voltage output terminal range is selected as -5V~+5V and the code value is set below the minimum code value corresponding to the range, the channel outputs -5V.

When the voltage output terminal range is selected as 0V~5V and the code value is set below the minimum code value corresponding to the range, the channel outputs 0V.

When the voltage output terminal range is selected as 1V~5V and the code value is set below the minimum code value corresponding to the range, the channel outputs 1V.