Technical Specifications
| PROFINET interface parameters | |
| Bus protocol | PROFINET |
| Number of slave stations | Determined by the number of slave stations supported by the master station |
| Data Transmission Medium | Ethernet CAT5 cable |
| Transmission rate | 100Mbps |
| Minimum cycle time[1] | 1ms |
| Transmission distance | ≤100m (inter-station distance) |
| Bus interface | 2×RJ45 |
| Maximum number of modules in series | 32 |
| Input and output process data volume | 1024Bytes[2] |
Note [1]: Cycle time (scan cycle) between PLC and coupler.
Note [2]: The total length of uplink and downlink data shall not exceed 1024 Bytes.
| Power supply parameters | |
| Input voltage | SELV Input24VDC(18V~36V) |
| Input current | Max:600mA(24VDC) |
| Backplane power supply current | Max:2A |
| Backplane power supply voltage | 5VDC |
| General technical specifications | ||
|
Specifications and dimensions |
100x27.82x80 mm |
|
|
Weight |
105g |
|
|
Usage environment |
Operating temperature |
-20℃~+60℃ |
|
Storage temperature |
-40℃~+80℃ |
|
|
Relative humidity |
95%, no condensation |
|
|
Altitude |
≤2000m |
|
|
Protection class |
IP20 |
|
|
Overvoltage category |
I |
|
|
Pollution level |
Level 2 |
|
| PROFINET IO RT | Supported |
| Automatic fault recovery | Supported |
| Hardware detection function | Supported |
| Diagnosis | Supported |
| Alarm | Supported |
| MRP | Supported |
| Firmware upgrade | Supported |
| Short circuit protection | Support (auto-recovery mechanism) |
| Reverse connection protection | Support (auto-recovery mechanism) |
| Surge protection | Supported |