Menu

Technical Specifications

Technical Specifications

PROFINET interface parameters
Bus protocol PROFINET
Number of slave stations Determined by the number of slave stations supported by the master station
Data Transmission Medium Ethernet CAT5 cable
Transmission rate 100Mbps
Minimum cycle time[1] 1ms
Transmission distance ≤100m (inter-station distance)
Bus interface 2×RJ45
Maximum number of modules in series 32
Input and output process data volume 1024Bytes[2]

Note [1]: Cycle time (scan cycle) between PLC and coupler.

Note [2]: The total length of uplink and downlink data shall not exceed 1024 Bytes.

 

Power supply parameters
Input voltage SELV Input24VDC(18V~36V)
Input current Max:600mA(24VDC)
Backplane power supply current Max:2A
Backplane power supply voltage 5VDC

 

General technical specifications

Specifications and dimensions

100x27.82x80 mm

Weight

105g

Usage environment

Operating temperature

-20℃~+60℃

Storage temperature

-40℃~+80℃

Relative humidity

95%, no condensation

Altitude

≤2000m

Protection class

IP20

Overvoltage category

I

Pollution level

Level 2

 

PROFINET IO RT Supported
Automatic fault recovery Supported
Hardware detection function Supported
Diagnosis Supported
Alarm Supported
MRP Supported
Firmware upgrade Supported
Short circuit protection Support (auto-recovery mechanism)
Reverse connection protection Support (auto-recovery mechanism)
Surge protection Supported