Indicator Description

Indicator Description

The indicators from top to bottom are  EIN, EOUT, RUN, CFG, BUS RUN, and BUS ERR

Status indicator RUN CFG EIN EOUT
On Power on Configuration exists    
Off Power failure No configuration    
Flashing EtherCAT IN connected EtherCAT OUT connected

 

Indicator Status Meaning
BUS RUN The green indicator is steadily lit The node is in the RUN state
The green indicator is periodically on for 200ms and off for 1000ms The node is in the STOP state
The green indicator is periodically on for 200ms and off for 200ms The node is in the pre-operational state
BUS ERR The green indicator is off CANopen network is normal
The green indicator is periodically on for 200ms and off for 1000ms The error counter of the CANopen controller reaches or exceeds the warning threshold
The green indicator is steadily lit BusOff