When the interfaces of the IO-Link master coupler are set to IO-Link and IO-Link slaves are connected, the event data addresses generated by the ports correspond as shown in the table below:

Input
Parameter Name Description Data Type Byte order
Event length Total number of existing master-side or slave-side events on the port (up to 255 stored simultaneously; when full, the earliest ones are overwritten) Byte 1
life cycle Power-on count (up to 255 counts are stored; when full, it is cleared and counting restarts) Byte 2
run time Runtime after power-on, in seconds; cleared to zero on power loss Dword 3-6

Event mode type

Bit7~Bit4 is mode:

0001: single short;

0010: disappeared;

0011: appeared;

 

Bit3~Bit0 is type:

0001: Notification;

0010: Warning;

0011: Error;

Word

7-8

event code

① Master-side event code of the port; see Appendix I "IO-Link Master EVENT CODE Codes".

② Slave-side event code of the port; the event code is defined by the connected IO-Link slave module.

Word

9-10

Output
Parameter Name Description Data Type Byte order

Port

Select the event port number to operate

Byte

1

Master or slave

Select master or slave event

0: Master;

1: Slave.

Byte

2

index

Event index to query (if more than the max number is entered, the last one is read)

Byte

3

clean

Clear all events on the slave side of this port (set to 1 to take effect)

Note: For the next configuration, it must be set to 0 and then to 1 to take effect

Byte

4

 

Previous