Mounting and Wiring

Pinout

Pin Definition Remarks
1 2 USBUS USBUS S-BusThe power supply USBUS is powered by the coupler and by the power supply Us of the EtherCAT coupler.
3 4 GND GND
5 6 RX0+ TX1+
7 8 RX0- TX1-
9 10 GND GND
11 12 TX0+ RX1+
13 14 TX0- RX1-
15 16 GND GND
17 18 AGND AO 1 Signal
19 20 AGND AO 2
21 22 AGND AO 3
23 24 AGND AO 4
25 26 NC NC
27 28 NC NC
29 30 NC NC
31 32 NC NC
33 34 0V Up 0V Up UpPeripheral voltage Up powers the electronic devices on the field side
35 36 0V Up 24V Up
37 38 24V Up 24V Up
39 40 SGND SGND

 


Pin Definition

Definition Description
USBUS S-Bus power supply 3.3V
GND S-Bus ground signal (Note: Never connect to 0V Up!)
RXn+ S-Bus receiving positive signal
RXn- S-Bus receiving negative signal
TXn+ S-Bus transmitting positive signal
TXn- S-Bus transmitting negative signal
AGND Analog output grounding
AO 1...AO 4 Analog output 1...4
NC Not Connected
0V Up Field side grounding signal
24V Up Field side power supply 24V
SGND Shield layer grounding

 


PDO Parameter Description

Name Data type Description
AO Outputs Channel 1 INT CH 1 output corresponding address
AO Outputs Channel 2 INT CH 2 output corresponding address
AO Outputs Channel 3 INT CH 3 output corresponding address
AO Outputs Channel 4 INT CH 4 output corresponding address

 


COE Parameter Description

COE parameters 0x8000~0x8030 are used for parameter settings of the analog output module. The parameters marked with yellow “  ” are reserved and cannot be configured. Note: when n takes values from 0 to 3, it corresponds to channels 1 to 4 respectively.

0x80n0 AO parameter setting
Index Name Meaning Symbol Default Value
80n0:01 Enable user scale Enable user scaling RW 0x00
80n0:02 Presentation Reserved parameter RW 0x00
80n0:05 Watchdog

0: The default watchdog value in index 0x80n0:13 takes effect.

1: Watchdog value (watchdog ramp)

The ramp defined in index 80n0:14 is activated when ramping to the watchdog value in index 80n0:13.

2: Last output value

If the watchdog timeout occurs, output the data from the last process.

RW 0x00
80n0:07 Enable user calibration Reserved parameter RW 0x00
80n0:08 Enable vendor calibration Reserved parameter RW 0x01
80n0:11 Offset Offset RW 0x0000
80n0:12 Gain

User scaling gain.

The gain is expressed in fixed-point format with a factor of 216.Value 1 corresponds to 65535 (0x00010000).

RW 0x00010000
80n0:13 Default output Output value in watchdog condition (when activated via Watchdog, index 80n0:05) RW 0x0000
80n0:14 Default output ramp

This value defines the ramp rate for ramping down to the default value.

The value is specified in digits per millisecond.For example, if the input is 100 and the default value is 0, in the event of a fault the output value changes from the maximum value (32767) to the default value in 327 milliseconds (32767/100).

RW 0xFFFF
80n0:15 User calibration offset Reserved parameter RW 0x0000
80n0:16 User calibration gain Reserved parameter RW 0xFFFF

 

 