SRI8200-8A0B COE Parameter Query

Object dictionary Sub-index Name Data Type Description

0x2000

0x01~

0x08

Port X01 Class B~

Port X08 Class B

BIT

This parameter is used to set the types of X01–X08:

0: Port is Class A

1: Port is Class B

 

0x09~

0x10

Port X01 IQ Output En~

Port X08 IQ Output En

BIT

The parameter is used to set the controllable IQ PNP output function of ports X01~X08:

0: Not controllable

1: Controllable

Note: This must be done in Class A port mode

0x2001

0x01

EtherCATBUSErrOutputEN

Byte

This parameter is used to set the action of the digital and analog output channels after the coupler's EtherCAT communication is disconnected:

0: Output hold, cleared after 50 ms

1: Output hold

2: Output hold, cleared after 10 ms

3: Output hold, cleared after 20 ms

4: Output hold, cleared after 100 ms

5: Outputs held for 500 ms and then cleared,

6: Output cleared immediately

0x2002


 

 

0x01 ExtNum Byte Number of connected IO-Link slave modules
0x02 LocalErr Byte Local module error

0x03 to 0x0A

EM1Err–EM8Err

Byte

Connected IO-Link slave module error;

0: No error;

1: Not connected or not configured.

0x2005 to 0x200C 0x01 index Word ISDU index of the IO-Link slave connected to ports X01–X08
0x02 subindex Byte ISDU sub-index of the IO-Link slave connected to ports X01–X08
0x03 Parameter length Byte Data width of the IO-Link slave connected to ports X01–X08 (max. 32 bytes)
0x04 Write Byte Write (value 1 valid); after being set to 1 successfully, the value is automatically reset to 0.
0x05 Read Byte Read (value 1 valid); after being set to 1 successfully, the value is automatically reset to 0.
0x06~0x25 byte1~byte32 Byte Parameter configuration of the IO-Link slaves connected to ports X01~X08
0x200D to 0x2014 0x01 event length Word Total number of master-side events already present on ports X01–X08; a maximum of 255 are stored at the same time, and when full, the oldest ones are overwritten.
0x02 event index Word Event index to be queried for ports X01–X08; if the entered value exceeds the maximum count, the last one is read.
0x03 Life cycle Word Power-up count of ports X01–X08; a maximum of 255 counts are stored at the same time, and counting restarts from zero when full.
0x04 run time Dword Power-on run time of ports X01~X08, in seconds; cleared on power-down.

0x05

Event mode type

Word

Bit7–Bit4 is mode:

0001: single short;

0010: disappeared;

0011: appeared;

Bit3~Bit0 is type:

0001: Notification;

0010: Warning;

0011: Error;

0X06 Event code word Master event codes of ports X01–X08; see the table "IO-Link Master EVENT CODE" for details.
0x07 Clear Word Clear all master-side events of ports X01–X08 (value 1 is valid); after it is set to 1 successfully, the value is automatically reset to 0.

0x2015 to 0x201C


 

 

 

 

 

 

0x01 event length Word Total number of slave-side events already present on ports X01–X08; a maximum of 255 are stored at the same time, and when full, the oldest ones are overwritten.
0x02 event index Word Event index to be queried for ports X01–X08; if the entered value exceeds the maximum count, the last one is read.
0x03 Life cycle Word Power-up count of ports X01–X08; a maximum of 255 counts are stored at the same time, and counting restarts from zero when full.
0x04 run time Dword Power-on run time of ports X01~X08, in seconds; cleared on power-down.

0x05

Event mode type

Word

Bit7–Bit4 is mode:

0001: single short;

0010: disappeared;

0011: appeared;

Bit3~Bit0 is type:

0001: Notification;

0010: Warning;

0011: Error;

0X06 Event code word Slave event codes of ports X01–X08; the event codes are defined by the connected IO-Link slave modules.
0x07 Clear Word Clear all slave-side events of ports X01–X08 (value 1 is valid); after it is set to 1 successfully, the value is automatically reset to 0.
0x4000 to 0x4070

0x01

Control

Byte

Control command:

0: no control

2: write

3: read

0x02

Status

Byte

Status feedback:

0: no activity

1: busy

2: success

4: error

0xFF: failure

0x03 Index Word ISDU index of the IO-Link slave connected to ports X01–X08
0x04 Subindex Byte ISDU sub-index of the IO-Link slave connected to ports X01–X08
0x05 Length Byte Data length (max 232 bytes supported)
0X06 Data ARRAY[0..231]OF BYTE Data
0x07 Error Code Word Error code 3.4.4 Error code query
0x6000 0x01 ID Word Coupler EtherCAT station address