Menu

Modbus-TCP address description

Modbus-TCP address description

For Modbus-TCP communication, the port is 502; the Modbus addresses are described as follows:

Communication timeout
Address Description Attribute

40353

(Low nibble valid; values above 5 are written as output hold)

Communication timeout (synchronized with the web page settings):
0: 200 ms
1: 500 ms
2: 1 s
3: 3 s
4: Output hold

R/W

ISDU configuration area
Address Description Attribute
40454-40473 40454 Select the port to configure (select the corresponding port in decimal) R/W
40455 ISDU index R/W
40456 (bit0–bit7) ISDU sub-index R/W
40456 (bit8–bit15) Data width (max 32 bytes) R/W
40457 (bit0–bit7) Write (set to 1 to take effect) R/W
40457 (bit8–bit15) Read (set to 1 to take effect) R/W
40458-40473 IO-Link slave function configuration R/W
Event query
Address Description Attribute
40474-40475 40474 (bit0–bit7) Select the event port number to operate R/W

40474 (bit8–bit15)

Select master or slave event
0: Master event
1: Slave event

R/W

40475 (bit0–bit7) Event index to query (if more than the max number is entered, the last one is read) R/W
40475 (bit8–bit15) Clear all master-side events of this port (set to 1 to take effect) R/W
Local digital output address
Address Description Attribute
40476 40476 (bit0–bit7) Local digital output address (C/Q Output-PIN4) R/W
40476 (bit8–bit15) Local digital output address (I/Q Output-PIN2)
IO-Link output address
Address Description Attribute
40477-40977 IO-Link slave module output data area (arranged in sequence according to the configured output bytes of the slave modules) R/W
ISDU input address
Address Description Attribute
40978-40994 40978 Port status after successful write or read (displays 1 after successful configuration) R
40979-40994 Slave function status after write or read R
Event input address
Address Description Attribute
40995-40999 40995 (bit0–bit7) Total number of master-side events already present on this port (a maximum of 255 are stored at the same time; when full, the oldest ones are overwritten) R
40995 (bit8–bit15) Power-on count (max 255) R
40996-40997 Run time after power-on in seconds, cleared on power-down R

40998

Indicates the event type
Bit4~Bit7 (high nibble): mode

1: single shot

2: disappeared

3: appeared
Bit0~Bit3 (low nibble): type

1: Notification

2: Warning

3: Error

R

40999

Event code; consult the slave manual for the corresponding description
Master:
0x1804: IO-Link mode C/Q short circuit
0x1805: PHY6360 over-temperature warning
0x1807: L+ power overcurrent
0x1813: C/Q mode overcurrent
0xFF21: IO-Link connected
0xFF22: IO-Link disconnected
Slave:
Event codes are defined by the connected IO-Link slave module.

R

Local digital input address
Address Description Attribute
41000 Local digital input address R
IO-Link input data address
Address Description Attribute
41001-41128 IO-Link slave module input data area (arranged in sequence according to the configured input bytes of the slave modules) R
Diagnostic information
Address Description Attribute

41129-41137

41129 (bit0–bit7)

Device status (error overview; see the detailed diagnostic information for the specific ports):

Bit0: Short-circuit error (short circuit on master/slave)

Bit1: Cascaded module error (a cascaded slave has a module short circuit)

Bit 2: station configuration error (total byte count mismatch or port software configuration inconsistent with the hardware configuration)

Bit3: Reserved

Bit4: Ua undervoltage

Bit5: Ua overvoltage

Bit6: Us undervoltage

Bit7: Us overvoltage

R

41129 (bit8–bit15) Reserved R

41130 (bit0–bit7)

IO-Link connection status:

(Bit0: Port X01; Bit1: Port X02, and so on)

0: Not connected

1: Connected

R

41130 (bit8–bit15)

Configuration status:

(Bit8: Port X01; Bit9: Port X02, and so on)

0: Configuration correct

1: Configuration error

 

Configuration error self-check:

(1) Port configuration bytes are less than the slave attributes (input/output bytes) or the configuration exceeds 32 bytes

(2) The configured port model is inconsistent with the actually connected model (including inconsistency between the extension modules configured by extension-capable slaves and the actual modules)

(3) Port type inconsistent with the slave type, e.g. Class B type without Ua connected (undervoltage)

R

41131 (bit0–bit7)

 

Master port Pin1 short circuit:

(Bit0: Port X01; Bit1: Port X02, and so on)

0: Normal

1: Short circuit

R

41131 (bit8–bit15)

Master port Pin4 short circuit:

(Bit8: Port X01; Bit9: Port X02, and so on)

0: Normal

1: Short circuit

R

41132 (bit0–bit7)

Short circuit in the slave module connected to the port:

(Bit0: Port X01; Bit1: Port X02, and so on)

0: Normal

1: Short circuit

R

41132 (bit8–bit15)

Port slave UA undervoltage:

(Bit8: Port X01; Bit9: Port X02, and so on)

0: Normal

1: Undervoltage

R

41133 (bit0–bit7)

Master port PIN2 short circuit:

(Bit0: Port X01; Bit1: Port X02, and so on)

0: Normal

1: Short circuit

R

41133 (bit8–bit15)

LED status:

(bit8: SF; bit9: BF)

0: Off

1: On

R

41134 (bit0–bit7)

For port X01:

Device status (0: Offline, 1: Online):

Bit0: Level 1 online status

Bit1: Level 2 online status

Bit2: Level 3 online status

Bit3: Level 4 online status

 

Short-circuit status (0: Normal, 1: Short circuit):

Bit4: Level 1 short-circuit status

Bit5: Level 2 short-circuit status

Bit6: Level 3 short-circuit status

Bit7: Level 4 short-circuit status

R

41134 (bit8–bit15)

For port X02:

Device status (0: Offline, 1: Online):

Bit8: Level 1 online status

Bit9: Level 2 online status

Bit10: Level 3 online status

Bit11: Level 4 online status

 

Short-circuit status (0: Normal, 1: Short circuit):

Bit12: Level 1 short-circuit status

Bit13: Level 2 short-circuit status

Bit14: Level 3 short-circuit status

Bit15: Level 4 short-circuit status

R

41135 (bit0–bit7)

For port X03:

Device status (0: Offline, 1: Online):

Bit0: Level 1 online status

Bit1: Level 2 online status

Bit2: Level 3 online status

Bit3: Level 4 online status

 

Short-circuit status (0: Normal, 1: Short circuit):

Bit4: Level 1 short-circuit status

Bit5: Level 2 short-circuit status

Bit6: Level 3 short-circuit status

Bit7: Level 4 short-circuit status

R

41135 (bit8–bit15)

For port X04:

Device status (0: Offline, 1: Online):

Bit8: Level 1 online status

Bit9: Level 2 online status

Bit10: Level 3 online status

Bit11: Level 4 online status

 

Short-circuit status (0: Normal, 1: Short circuit):

Bit12: Level 1 short-circuit status

Bit13: Level 2 short-circuit status

Bit14: Level 3 short-circuit status

Bit15: Level 4 short-circuit status

R

41136 (bit0–bit7)

For port X05:

Device status (0: Offline, 1: Online):

Bit0: Level 1 online status

Bit1: Level 2 online status

Bit2: Level 3 online status

Bit3: Level 4 online status

 

Short-circuit status (0: Normal, 1: Short circuit):

Bit4: Level 1 short-circuit status

Bit5: Level 2 short-circuit status

Bit6: Level 3 short-circuit status

Bit7: Level 4 short-circuit status

R

41136 (bit8–bit15)

For port X06:

Device status (0: Offline, 1: Online):

Bit8: Level 1 online status

Bit9: Level 2 online status

Bit10: Level 3 online status

Bit11: Level 4 online status

 

Short-circuit status (0: Normal, 1: Short circuit):

Bit12: Level 1 short-circuit status

Bit13: Level 2 short-circuit status

Bit14: Level 3 short-circuit status

Bit15: Level 4 short-circuit status

R

41137 (bit0–bit7)

For port X07:

Device status (0: Offline, 1: Online):

Bit0: Level 1 online status

Bit1: Level 2 online status

Bit2: Level 3 online status

Bit3: Level 4 online status

 

Short-circuit status (0: Normal, 1: Short circuit):

Bit4: Level 1 short-circuit status

Bit5: Level 2 short-circuit status

Bit6: Level 3 short-circuit status

Bit7: Level 4 short-circuit status

R

41137 (bit8–bit15)

For port X08:

Device status (0: Offline, 1: Online):

Bit8: Level 1 online status

Bit9: Level 2 online status

Bit10: Level 3 online status

Bit11: Level 4 online status

 

Short-circuit status (0: Normal, 1: Short circuit):

Bit12: Level 1 short-circuit status

Bit13: Level 2 short-circuit status

Bit14: Level 3 short-circuit status

Bit15: Level 4 short-circuit status

R

 

Previous
Data address description
Next
S7-TCP address description