Menu

Mounting and Wiring

Pinout

Pin Definition Remarks
1 2 USBUS USBUS S-BusThe power supply USBUS is powered by the coupler and by the power supply Us of the EtherCAT coupler.
3 4 GND GND
5 6 RX0+ TX1+
7 8 RX0- TX1-
9 10 GND GND
11 12 TX0+ RX1+
13 14 TX0- RX1-
15 16 GND GND
17 18 R3+ R1+ Signal
19 20 RL3+ RL1+
21 22 R3- R1-
23 24 R4+ R2+
25 26 RL4+ RL2+
27 28 R4- R2-
29 30 NC NC
31 32 NC NC
33 34 NC NC UpThe device has no upper contacts and is powered solely via USBUS.
35 36 NC NC
37 38 NC NC
39 40 SGND SGND

 


Pin Definition

Definition Description
USBUS S-Bus power supply 3.3V
GND S-Bus ground signal (Note: Never connect to 0V Up!)
RXn+ S-Bus receiving positive signal
RXn- S-Bus receiving negative signal
TXn+ S-Bus transmitting positive signal
TXn- S-Bus transmitting negative signal
R1+ Input R1+
RL1+ Input RL1+
R1- Input R1-
R2+ Input R2+
RL2+ Input RL2+
R2- Input R2-
R3+ Input R3+
RL3+ Input RL3+
R3- Input R3-
R4+ Input R4+
RL4+ Input RL4+
R4- Input R4-
NC Not Connected
SGND Shield layer grounding

 


PDO Parameter Description

Name Parameters Data type Description
Status Underrange Bit Data is below the measurement range
Overrange Bit Data is over the limit
Error Bit 0: No error1: If data is invalid (over or below the measurement range)
TxPDO State Bit Reserved parameter
TxPDO Toggle Bit Reserved parameter
Value / INT Input channel data

 


COE Parameter Description

COE parameters 0x8000~0x8030 are used for parameter settings of the RTD module. The parameters marked with yellow “  ” are reserved parameters and cannot be configured. Note: when n takes values from 0 to 3, it corresponds to channels 1 to 4 respectively.

0x80n0 RTD parameter settings
Index Name Meaning Symbol Default Value
80n0:01 Enable user scale Enable user scaling RW 0x00
80n0:02 Presentation Reserved parameter RW 0x00
80n0:05 Siemens bits Reserved parameter RW 0x00
80n0:0A Enable user calibration Reserved parameter RW 0x00
80n0:0B Enable vendor calibration Reserved parameter RW 0x01
80n0:11 User scale offset User scaling offset RW 0x0000
80n0:12 User scale gain User scaling gain.The gain is expressed in fixed-point format with a factor of 216.Value 1 corresponds to 65535 (0x00010000). RW 0x00010000
80n0:15 Filter settings Reserved parameter RW 0x0000
80n0:17 User calibration offset Reserved parameter RW 0x0000
80n0:18 User calibration gain Reserved parameter RW 0xFFFF
80n0:19 RTD element RTD type:0:PT100(-200℃...850℃)2:PT1000(-200℃...850℃) RW 0x0000
80n0:1A Connection technology Reserved parameter RW 0x0000
80n0:1B Wire calibration 1/32 Ohm Reserved parameter RW 0x0000

 


 

Previous
Technical Specifications
Next
SC3284 | Analog Module
Last modified: 2026-03-25