Menu

Technical Specifications

Technical Specifications

Product Model SC3248
Technical specifications
Number of input channels 8 (single-ended input)
Measurement type Current type
Current range 4~20mA
Internal resistance 85Ω (typical value)
Input filtering cutoff frequency 1KHz
Conversion time Default 1.25ms, configurable
Resolution 16-bit
Measurement error (total measurement range) <±0.3% (relative to the full scale value)
S-bus current consumption Typical value 130 mA
Electrical isolation 500 V (S-bus/signal voltage)
Insulation strength Maximum 30V
Operating environment Operating environment temperature: -20~60°C, relative humidity: 5%~90% (Non-condensing)
Storage temperature -40~60 °C
Dimensions (L × W × H) 12×66×55(mm)

 