Menu

Technical Specifications

Technical Specifications

Product Model SC3274
Technical specifications
Input quantity 4
Connection method Two-wire or three-wire system (default: three-wire system)
Input filtering cutoff frequency Typical value 1 kHz
Sensor type Pt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, resistance measurement (e.g., potentiometer, 10 Ω…1/4 kΩ), KTY sensors
Conversion time The default setting is approximately 170 ms
Measurement current Typical value < 0.5 mA (depending on load)
Measurement range -200 ℃ .. +850 ℃ (platinum sensor); -60°C .. +250°C (nickel sensor)
Temperature range Range dependency: -200 ℃ .. +850 ℃ (platinum sensor); -60°C .. +250°C (nickel sensor)
Resolution 0.1°C per digit
Measurement error <±0.5°C (for Pt sensor, 4x 3-wire connection)
Electrical isolation 500 V (S-bus/field voltage)
S-bus current consumption Typical value 160 mA
Operating environment Operating environment temperature: -20~60°C, relative humidity: 5%~90% (Non-condensing)
Storage temperature -40~60 °C
Dimensions (L × W × H) 12×66×55(mm)

 

Previous
Indicator Description
Next
Mounting and Wiring
Last modified: 2026-03-25