Indicator Description

Indicator Description

Indicator label Color Status Device status Description
RUN Green Off Initializing EtherCAT state machine status: INT = Plug-in module initializing
Flashing Pre-operational EtherCAT state machine status: PRE-OP = Mailbox communication enabled and different default settings active
Single flash Safe operation EtherCAT state machine status: SAFE-OP = Synchronization manager channels and distributed clocks verified. Outputs remain in safe state
Steadily lit Operational EtherCAT state machine status: OP = Normal operating state
Up Green Steadily lit - 24V DC power supply connected
Off - 24V DC power supply not connected
I1-I16 Green Steadily lit - Signal voltage "1" (0V...7V)Signal voltage "1" (11V...30V)
Off - Signal voltage "0" (18V...30V)Signal voltage "0" (-3V...5V)