Mounting and Wiring

Product image

 


SRI8200-4A0B-E COE Parameter Query

Object dictionary Sub-index Name Data Type Description
0x2000 0x01~0x04 Port X01 Class B~Port X04 Class B Bit

This parameter is used to set the types of X01–X04:

0: Port is Class A

1: Port is Class B

0x05~0x08 Port X01 IQ Output En~Port X04 IQ Output En Bit

The parameter is used to set the controllable IQ PNP output function of ports X01~X04:

0: Not controllable

1: Controllable

Note: This must be done in Class A port mode

0x2001 0x01 EtherCATBUSErrOutputEN Byte

This parameter is used to set the action of the digital and analog output channels after the coupler's EtherCAT communication is disconnected:

0: Output hold, cleared after 50 ms

1: Output hold

2: Output hold, cleared after 10 ms

3: Output hold, cleared after 20 ms

4: Output hold, cleared after 100 ms

5: Outputs held for 500 ms and then cleared,

6: Output cleared immediately

0x2002

 

 

0x01 ExtNum Byte Number of connected IO-Link slave modules

0x02

LocalErr

Byte

Local master module system fault information:

0: No fault

1: System fault

0x03 to 0x06

EM1Err–EM4Err

Byte

IO-Link slave module connection information:

0: Connected slave mode;

1: Slave module not connected or not configured.

0x2005 to 0x2008

 

 

 

 

 

0x01 index Word ISDU index of the IO-Link slave connected to ports X01–X04
0x02 subindex Byte ISDU sub-index of the IO-Link slave connected to ports X01–X04
0x03 Parameter length Byte Data width of the IO-Link slaves connected to ports X01~X04 (maximum 32 bytes)
0x04 Write Byte Write (value 1 is valid); after it is set to 1 successfully, the value is automatically reset to 0.
0x05 Read Byte Read (value 1 is valid); after it is set to 1 successfully, the value is automatically reset to 0.
0x06~0x25 byte1~byte32 Byte Parameter configuration of the IO-Link slaves connected to ports X01~X04.

0x200D to 0x2010

 

 

 

 

 

 

0x01 event length Word Total number of existing master-side events of ports X01~X04; up to 255 are stored simultaneously, and when full, the earliest ones are overwritten.
0x02 event index Word Event index to be queried for ports X01–X04; if the entered value exceeds the maximum count, the last one is read.
0x03 Life cycle Word Power-up count of ports X01–X04; a maximum of 255 counts are stored at the same time, and counting restarts from zero when full.
0x04 run time Dword Power-up runtime of ports X01–X04, in seconds; cleared to zero on power loss.

0x05

Event mode type

Word

Bit7~Bit4 is mode:

0001: single short;

0010: disappeared;

0011: appeared;

Bit3~Bit0 is type:

0001: Notification;

0010: Warning;

0011: Error;

0X06 Event code word Master event codes of ports X01~X04; see the table "IO-Link Master EVENT CODE Codes".
0x07 Clear Word Clear all master-side events of ports X01~X04 (value 1 valid); after being set to 1 successfully, the value is automatically reset to 0.

0x2015 to 0x2018

 

 

 

 

 

 

0x01 event length Word Total number of existing slave-side events of ports X01~X04; up to 255 are stored simultaneously, and when full, the earliest ones are overwritten.
0x02 event index Word Event index to be queried for ports X01–X04; if the entered value exceeds the maximum count, the last one is read.
0x03 Life cycle Word Power-up count of ports X01–X04; a maximum of 255 counts are stored at the same time, and counting restarts from zero when full.
0x04 run time Dword Power-up runtime of ports X01–X04, in seconds; cleared to zero on power loss.

0x05

Event mode type

Word

Bit7~Bit4 is mode:

0001: single short;

0010: disappeared;

0011: appeared;

Bit3~Bit0 is type:

0001: Notification;

0010: Warning;

0011: Error;

0X06 Event code word Slave event codes of ports X01~X04; the event codes are defined by the connected IO-Link slave modules.
0x07 Clear Word Clear all slave-side events of ports X01~X04 (value 1 valid); after being set to 1 successfully, the value is automatically reset to 0.

0x4000 to 0x4030

 

 

 

 

 

 

0x01

Control

Byte

Control command:

0: no control

2: write

3: read

0x02

Status

Byte

Status feedback:

0: no activity

1: busy

2: success

4: error

0xFF: failure

0x03 Index Word ISDU index of the IO-Link slave connected to ports X01–X04
0x04 Subindex Byte ISDU sub-index of the IO-Link slave connected to ports X01–X04
0x05 Length Byte Data length (max 232 bytes supported)
0X06 Data ARRAY[0..231]OF BYTE Data
0x07 Error Code Word Error code 3.4.4 Error code query
0x6000 0x01 ID Word Coupler EtherCAT station address

 

 