Technical Specifications
SRL3284 Technical Specifications
Model |
SRL3284 |
Technical Specifications |
|
Number of input points |
4 |
Input Type |
Thermocouple |
Supply polarity protection |
Support |
Operating voltage |
24VDC (allowable voltage range: 18VDC~28VDC) |
Bus 5VDC current consumption |
165mA |
Input range |
Thermocouple type (any one): S/T/R/E/N/K/J; Voltage range: ±80mV |
Principle of Measurement |
Sigma -Delta |
Resolution |
|
Temperature |
0.1°C/0.1°F |
Voltage |
15 bits + sign bit |
Common mode rejection |
85dB, DC-50HZ/60HZ/400HZ |
Length of conductor |
Maximum length of compensating conductor is 30m |
Loop resistance of conductor |
Max. 20Ω |
Input impedance |
≥10MΩ |
Essential Error |
≤0.1%FS |
Consistency |
0.05%FS |
Cold junction error |
±1.5°C |
Isolate |
|
Between Channel and Bus |
Yes |
Between the power supply and the bus |
Yes |
Between the channel and the power supply |
Yes |
Display indication |
Power, RUN green indicator |
Operating Conditions |
|
Operating temperature |
Operating environmental conditions: -20~60°C, relative humidity: 5%~90% (no condensation) |
Dimensions (L×W×H) |
15×100×80 (mm) |
SRL3274 Technical Specifications
Model |
SRL3274 |
Technical Specifications |
|
Number of input points |
4 |
Input Type |
RTD |
Supply polarity protection |
Support |
Operating voltage |
30V DC |
Bus 5VDC current consumption |
165mA |
Input range |
Type of RTD (optional): Pt-100Ω, 1000Ω (α=3850PPM, 3920PPM, 3850.55PPM, 3916PPM, 3902PM); Ni-100Ω, 1000Ω (α=6720PPM, 6178PPM); |
Principle of Measurement |
Sigma -Delta |
Data word |
-32768 to +32767 |
Resolution |
|
Temperature |
0.1°C/0.1°F |
Voltage |
--- |
Resistance |
15 bits + sign bit |
Measurement transition time |
less than 400ms |
Common mode rejection |
greater than 125dB, AC120V |
Cable length (compensating conductor) |
Max. 30m |
loop resistance of conductor |
max. 100Ω |
Input impedance |
≥1MΩ |
Essential Error |
≤0.1%FS |
Consistency |
0.05%FS |
Cold junction error |
--- |
Isolate |
|
Between Channel and Bus |
Yes |
Between the power supply and the bus |
Yes |
Between the channel and the power supply |
Yes |
Display indication |
Power supply green LED display |
Operating Conditions |
|
Operating temperature |
Operating environmental conditions: -20~60°C, relative humidity: 5%~90% (no condensation) |
Dimensions (L×W×H) |
15×100×80 (mm) |
Last modified: 2025-06-30