SRT8200 comes with 2 Byte Status Word and 2 Byte Control Word.

Status Word: Adapter Status (specific functions have not been opened yet). Control Word: Adapter Configuration, which is currently open to two bits.

  1. The Configuration Enable bit is the system parameter configuration bit. If each module parameter needs to be configured, write the module parameter to be configured (see the module manual for details), and set Configuration Enable to 1, then the configuration of each module parameter will take effect.

Note during module parameter configuration: in the plc initialization program, first set all module parameters according to the definition of each module control word, and then enable the parameter configuration bit of the coupler to make the parameter configuration effective; The second modification of module parameter configuration takes effect only after the module is powered off and restarted once.

  1. The Outputs Hold bit is the output module holding bit. When the SRT8200 is disconnected from the PLC, all the output modules of the SRT8200 are cleared by default. If the output holding function is required, set the Outputs Hold to 1.

Note that the Outputs Hold bit can only be modified once and will enable the output holding function until the SRT8200 is powered on again.