Technical Specifications

SRC3601 Technical Specifications

Interface Parameters
Bus protocol S-Link
Process Data Volume: Downlink 20 Bytes
Process Data Volume: Uplink 30 Bytes
Technical Specifications
Measured value Voltage and current
Calculation parameter Active power, reactive power, apparent power, power factor, and frequency
Measuring voltage range Max 690VAC
Measuring current range (continuous operation) 5A
Voltage input impedance (typical value) 990kΩ
Current input impedance (typical value) 30mΩ
Resolution 24 bit
Frequency range 45Hz~65Hz
Accuracy of sinusoidal voltage and current measurement (full range) Voltage
Current 0.2%
Power (calculated value) 0.5%
Frequency ±0.003Hz
Sample rate ≤8ksps
Current consumption (typical value) 115mA
Operating temperature -10°C~+60°C
Storage temperature -20°C to +75°C
Relative humidity 95%, no condensation
Weight 75g
Dimensions 100×14.8×68.67mm
Degree of protection IP20

SRC3602 Technical Specifications

Interface Parameters
Bus protocol S-Link
Process Data Volume: Downlink 60 Bytes
Process Data Volume: Uplink 90 Bytes
Technical Specifications
Measured value Voltage and current
Calculation parameter Active power, reactive power, apparent power, power factor, and frequency
Measuring voltage range (continuous operation) Direct measurement
Measurement by voltage transformer (the transformation ratio of the transformer is PT) PT×120V
Measuring current range (continuous operation) Direct measurement
Measurement by current transformer (the transformation ratio of the transformer is CT) CT×5A
Voltage input impedance (typical value) 330kΩ
Current input impedance (typical value) 30mΩ
Resolution 24 bit
Frequency range 45Hz~65Hz
Accuracy of sinusoidal voltage and current measurement (full range) Voltage
Current 0.2%
Power (calculated value) 0.5%
Frequency ±0.003Hz
Sample rate ≤8ksps
Current consumption (typical value) 115mA
Operating temperature -10°C~+60°C
Storage temperature -20°C to +75°C
Relative humidity 95%, no condensation
Weight 75g

SRC3603 Technical Specifications

Interface Parameters
Bus protocol S-Link
Process Data Volume: Downlink 20 Bytes
Process Data Volume: Uplink 30 Bytes
Technical Specifications
Measured value Voltage and current
Calculation parameter Active power, reactive power, apparent power, power factor, and frequency
Measuring voltage range Max 690VAC
Measuring current range (continuous operation) 5A
Voltage input impedance (typical value) 990kΩ
Current input impedance (typical value) 30mΩ
Resolution 24 bit
Frequency range 45Hz~65Hz
Accuracy of sinusoidal voltage and current measurement (full range) Voltage
Current 0.2%
Power (calculated value) 0.5%
Frequency ±0.003Hz
Sample rate ≤8ksps
Current consumption (typical value) 115mA
Operating temperature -10°C~+60°C
Storage temperature -20°C to +75°C
Relative humidity 95%, no condensation
Weight 75g
Dimensions 100×14.8×68.67mm
Degree of protection IP20

SRC3604 Technical Specifications

Interface Parameters
Bus protocol S-Link
Process Data Volume: Downlink 60 Bytes
Process Data Volume: Uplink 90 Bytes
Technical Specifications
Measured value Voltage and current
Calculation parameter Active power, reactive power, apparent power, power factor, and frequency
Measuring voltage range Max 690VAC
Measuring current range (continuous operation) 5A
Voltage input impedance (typical value) 990kΩ
Current input impedance (typical value) 30mΩ
Resolution 24 bit
Frequency range 45Hz~65Hz
Accuracy of sinusoidal voltage and current measurement (full range) Voltage
Current 0.2%
Power (calculated value) 0.5%
Frequency ±0.003Hz
Sample rate ≤8ksps
Current consumption (typical value) 115mA
Operating temperature -10°C~+60°C
Storage temperature -20°C to +75°C
Relative humidity 95%, no condensation
Weight 75g
Dimensions 100×14.8×68.67mm
Degree of protection IP20